Categories | Cable Fire Resistance Tester |
---|---|
Brand Name: | GOLD |
Model Number: | GD-IEC60332-1-2 |
Certification: | ISO |
Place of Origin: | CHINA |
MOQ: | 1set |
Price: | USD 3000-3500/set |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability: | 5 Set per month |
Delivery Time: | 30days |
Packaging Details: | Standard Wooden Case |
Name: | Single Wire And Cable Vertical Combustion Tester |
Standard: | IEC 60332-1-1.2.3 |
Size: | Length 1.35 * Width 0.78 * Height 1.95 meters |
Power: | 1.35 * Width 0.78 * Height 1.95 meters |
Gas source: | propane, air (to be provided by the customer) |
Ignition power: | 1 kw |
IEC 60332-1-2 Single Insulated Wire And Cable Vertical Combustion Tester
Single Wire And Cable Vertical Combustion Tester Production introduction:
The single wire and cable vertical combustion tester is mainly used
to detect the flame retardant properties of the insulating
materials of wires and cables under abnormal working conditions
(such as overheating, overload or short circuit). The equipment
strictly simulates the flame spread of the cable when it is laid
vertically. It can accurately evaluate the speed of the flame
spreading along the longitudinal direction of the sample and
simultaneously observe the ignition effect of the molten dripping
during the combustion process. The combustion box door must be kept
open during the test (Note: The box door is designed only for
equipment protection and daily dust prevention. According to the
requirements of the standard test procedures, it must be opened
during the experiment to ensure air circulation and observation
field). This device complies with international general flame
retardant test standards and is widely used in the verification of
fire safety performance of power cables, communication cables and
optical fiber composite cables.
Single Wire And Cable Vertical Combustion Tester Standards:
1. IEC 60332-1-1
- Name: Tests on electric and optical fibre cables under fire
conditions - Part 1-1: Test for vertical flame propagation for a
single insulated wire or cable
- Scope: Vertical flame test for a single wire or cable (flame
height 20mm).
2. IEC 60332-1-2
- Name: Test for vertical flame propagation for a single insulated
wire or cable - Procedure for 1 kW pre-mixed flame
- Scope: Vertical flame test using 1kW pre-mixed flame (flame
height 125mm).
3. IEC 60332-1-3
- Name: *Test for vertical flame propagation for a single insulated
wire or cable - Procedure for determination of flaming
droplets/particles*
- Scope: Additional test for evaluating molten droplets during
combustion.
International and regional equivalent standards
European standards (EN)
4. EN 60332-1-1/1-2/1-3
- Completely equivalent to IEC standards, applicable to EU CE certification (such as CPR regulations) and UKCA certification.
US standards
5. UL 1581
- Section VW-1: Vertical burning test (similar to IEC 60332-1-2, but the flame intensity and judgment criteria are different).
6. UL 2556
- References the IEC 60332 series and is applicable to flame propagation testing of wires and cables.
7. NFPA 262 (ASTM E662)
- Optical cable burning test (some methods are complementary to IEC 60332).
Chinese Standard (GB/T)
8. GB/T 18380.11-2022
- Equivalent to IEC 60332-1-1 (single vertical burning, 20mm
flame).
9. GB/T 18380.12-2022
- Equivalent to IEC 60332-1-2 (1kW flame vertical burning).
Japanese Standard (JIS)
10. JIS C 3005
- References IEC 60332-1 series for fire performance testing of
wires and cables.
Canadian Standard
11. CSA C22.2 No. 0.6
- Vertical burning test requirements, similar to UL VW-1.
Australian/New Zealand Standard
12. AS/NZS IEC 60332.1.1/1.2
- Directly adopts IEC standards, applicable to the Australian and
New Zealand markets.
International Railway Standards
13. EN 45545-2 (Railway)
- References the IEC 60332 series of tests for the fire performance
of cables.
Single Wire And Cable Vertical Combustion Tester Specifications:
Overall Dimensions | 630mm(W) * 600mm(D) * 2170mm(H) |
Power Supply | AC 220V, 50/60Hz, 2A |
Air Source | propane and air (provided by customers) |
Single Wire And Cable Vertical Combustion Tester Technical Parameters:
● SUS304 stainless steel control box, fume hood, and metal cover
are integrated for easy operation and beautiful appearance;
● Metal cover size: 300mm×450mm×1200mm, open on the front, closed
on the top and bottom;
● Blowtorch: nominal power is 1kw;
● Control mode: touch screen control, the test burning time is set
on the screen, and the burning time can be controlled and the
temperature value can be displayed during flame temperature
calibration;
● Ignition device: automatic high-pressure ignition;
● Flowmeter: air rotor flowmeter adjustable from 1.5 to 15L/min,
propane rotor flowmeter adjustable from 0.1 to 1L/min;
● A separately controlled exhaust fan is installed on the top;
● Flame detection device: one φ0.5K imported thermocouple, one
electrolytic copper block with an outer diameter of φ9mm and a mass
of 10g±0.05g, and a set of temperature and time display devices.
![]() |