Categories | Transformer Oil Regeneration |
---|---|
Brand Name: | REXON |
Model Number: | ZYD-I-150 |
Certification: | CE, ISO, SGS, CCC |
Place of Origin: | China |
Function: | Transformer Oil Regeneration |
Flow Rate: | 9000 L/H |
Breakdown Voltage (Dielectric Strength): | ≥75 KV-85 KV |
Acid Content: | ≤0.01 mg koH/g |
Gas Content: | ≤0.1% |
Oil Water Content: | 3 PPM |
Filter Elements: | Three Stages |
Filtration Fineness: | 1 Micron |
Regenreation Material: | Silica Gel |
Vacuum Type: | Double Stages |
Ultimate Vacuum: | 3~5 Pa |
Working Vacuum: | 0.08 ~-0.099 Mpa |
Electric Heating Power: | 135 KW |
Total Power: | 149 KW |
Working Temperature: | 20~80 ℃ |
Power Supply: | 3Phase, 380VAC, 50Hz or As Required |
Material: | Carbon Steel |
Color: | Blue, Grey, White, Yellow Etc. |
Application
Rexon ZYD-I-150 Transformer Oil Regeneration and Recycling Plant, is a high vacuum oil dehydration, oil degassing and oil filtration system combined with a high efficient oil regeneration device which contains sufficient silica gel material for oil regeneration process. This oil regeneration system is especially applied to regenerate used and aging transformer oil, insulating oil. Series ZYD-I system can deal with not only low voltage oil, but also high voltage oil like 110KV, 500KV, 1000KV. It can perform a perfect and super high efficient oil purification, oil filtration and oil recycling process to old transformer oil.
The series ZYD-I Double-stage vacuum transformer oil regeneration and recycling plant not only provide dewaters, degases and remove impurities, but also remove acidity, sludge, free carbon, deep oxide, and other soluble oil decay products and discoloration. And it can improve the voltage and make the every index like acid value, PH value, of the insulation oil reach the national standard and improve the insulation oil's index. This is accomplished by the use of high vacuum degasification technology and particulate filters combined with our special silica gel. After treating, the oil can be reused as new.
As an important on-site transformer oil cleaning and transformer maintenance system, this plant can inject oil into the transformers online too. It can be used as an independent vacuum resource plant to vacuum transformers high efficiently.
Features
1. Double-stage vacuum system, strong power of vacuum evacuating,
ultimate vacuum value ≤ 5Pa.
2. Oil Regeneration Device for oil color, acid and oil smell
reconditioning.
3. Big capacity of moisture and gas separating chambers, efficient
oil film sprayer, increasing separating size and separating time to
ensure the dry-level and dielectric strength of oil improving
greatly.
4. Duplex-stereo film evaporation technology, combined with unique
and advanced dewatering, and degassing components, can rapidly and
effectively separate water, and gas from oil.
5. Multi-stage precision filtration system, mesh filtration
combined with molecular adsorption technologies, which can purify
oil highly efficiently and make oil highly pure.
6. Efficient electric heating system, heating uniformity, less
power consumption, safe, and reliable.
7. Double-infrared liquid level sensor, pressure protective system,
and foaming elimination system to ensure the machine operates
easily and safely.
8. Adopt an interlocked protective system, which connects the oil
pump, heater, and liquid level sensor, avoiding blank heating,
blank pumping, oil leaks, and electricity leaks. If there is any
fault, the machine will be powered off automatically.
9. It can be operated both online and offline by transformers.
10. Can be used independent device for vacuuming transformers that
are above 110KV and can vacuum oil filling for power equipment.
11. Can work online for 150 hours continuously, highly reliable and
long time running.
12. PLC programming control system and touch screen to achieve
machine working fully automatically.
13. Mobile trailer and weather-proof enclosure are available for option.
Advantages
By regenerating the transformer oil, it restores the oil's original
quality, ensuring optimal performance of the transformer. And helps extend the lifespan of transformers, reducing the need
for costly replacements and increasing overall operational
efficiency. The regeneration process not only restores the oil but also helps
reduce waste generation. By reusing the existing oil, the equipment
contributes to environmental sustainability by minimizing the
disposal of used transformer oil.
Technical Parameters
Parameters | Model Unit | ZYD-I -30 | ZYD-I -50 | ZYD-I -80 | ZYD–I -100 | ZYD-I -150 | ZYD-I -200 | ZYD-I -250 | ZYD-I -300 | |||||||||||||||||||
Flow Rate | L/hr | 1800 | 3000 | 4800 | 6000 | 9000 | 12000 | 15000 | 18000 | |||||||||||||||||||
Working Vacuum | MPa | -0.08 ~ -0.099 | ||||||||||||||||||||||||||
Working Pressure | MPa | ≤ 0.3 | ||||||||||||||||||||||||||
Temperature Control Range | ℃ | 20 ~ 80 | ||||||||||||||||||||||||||
Operation Temperature | ℃ | 50 ~ 70(55~60 is best) | ||||||||||||||||||||||||||
Power Supply | 380V, 3 Phase, 50Hz (or as per requirements) | |||||||||||||||||||||||||||
Working hours without Trouble | Hour | 4000 | ||||||||||||||||||||||||||
Continuous Working Hours | Hour | 200 | ||||||||||||||||||||||||||
Working Noise | dB(A) | 75 | 75 | 75 | 75 | 80 | 80 | 80 | 80 | |||||||||||||||||||
Heating Power | KW | 30 | 60 | 75 | 90 | 135 | 150 | 165 | 180 | |||||||||||||||||||
Total Power | KW | 35 | 67.5 | 83 | 101.5 | 149 | 164 | 179 | 198 | |||||||||||||||||||
Inlet/Outlet | mm | φ25 | φ32 | φ38 | φ42 | φ50 | φ50 | φ60 | φ60 | |||||||||||||||||||
Weight | Kg | 550 | 650 | 900 | 1000 | 1250 | 1550 | 1700 | 2050 | |||||||||||||||||||
Overall | Length | mm | 1550 | 1620 | 1730 | 1750 | 1970 | 2050 | 2150 | 2250 | ||||||||||||||||||
Width | mm | 1450 | 1520 | 1550 | 1620 | 1820 | 2070 | 2120 | 2200 | |||||||||||||||||||
Height | mm | 1520 | 1560 | 1620 | 1760 | 1970 | 2020 | 2100 | 2190 | |||||||||||||||||||
Regeneration Material (Silica Gel Quantity KGS) | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | ||||||||||||||||||||
Oil Data After Treatment
|
![]() |