Overview
ATL-957 short circuit isolators are used for the short circuit
fault protection of buses. When a bus circuit is operating
normally, the GL-957 short circuit isolator will not operate; when
a short circuit fault occurs at a place at the output end of the
short circuit isolator in the bus circuit (short-circuit current
>200mA), the section suffering the short circuit fault will be cut
off from the bus, thus ensuring the normal communication of the
other sections of the bus. Upon elimination of the short circuit
fault, the short circuit isolator can automatically bring the
isolated section into the system again. A short circuit isolator
will make it convenient to confirm the location suffering a short
circuit fault. The short circuit isolator does not need coding nor
occupies the address in the bus circuit.
Main technical parameters
1. Mode of operation: Nonpolar two-wire system
2. Quiescent current: <5.0mA
3. Operative current: >200mA
4. Operation indicator: Red (It is out in the normal monitoring
status or remains lit in the operation status)
5. Operating environment: Temperature: -10℃~50℃; relative humidity:
≤95% (40℃±2℃, without condensation)
6. External dimensions: 86×86×40mm (with the base)
7. Weight: about 125g (with the base)